Latest Measurement of Power MCQ Objective Questions
Top Measurement of Power MCQ Objective Questions
Measurement of Power Question 1:
In the measurement of 3-phase power using two wattmeter method, the value of phase angle when the two wattmeter reads equal reading is:
Answer (Detailed Solution Below)
Measurement of Power Question 1 Detailed Solution
Power measurement using two wattmeter method
According to Blondel's Theorem, for 'n' phase power measurement, the no. of wattmeters required is 'n-1'.
Therefore, for the 3-phase circuit, 3-1 = 2 wattmeters are required.
The total 3ϕ power is the sum of the power measured by individual wattmeters.
\(W=W_1+W_2\)
The reading of the wattmeters is given by:
\(W_1=V_LI_Lcos(30+ϕ)\)
\(W_2=V_LI_Lcos(30-ϕ)\)
The total power is given by:
\(W_1+W_2=\sqrt{3}V_LI_Lcosϕ\)
Calculation
The value of phase angle (ϕ) is given by:
\(ϕ=tan^{-1}[{\sqrt{3}(W_1-W_2)\over W_1+W_2}]\)
If W1 = W2
\(ϕ=tan^{-1}(0)\)
ϕ = 0°
Important Points
p.f. angle (ϕ) |
p.f.(cos ϕ) |
W1 [VLIL cos (30 + ϕ)] |
W2 [VLIL cos (30 - ϕ)] |
W = W1 + W2 [W = √3VLIL cos ϕ] |
Observations |
0° |
1 |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
√3 VLIL |
W1 = W2 |
30° |
0.866 |
\(\frac{{{V_L}I}}{2}\) |
VLIL |
1.5 VL IL |
W2 = 2W1 |
60° |
0.5 |
0 |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
W1 = 0 |
90° |
0 |
\(\frac{{ - {V_L}{I_L}}}{2}\) |
\(\frac{{{V_L}{I_L}}}{2}\) |
0 |
W1 = -ve W2 = +ve |
Measurement of Power Question 2:
In case of the two-wattmeter method for measuring the power of a balanced 3ϕ load, the whole power is measured by one of the two wattmeters when:
Answer (Detailed Solution Below)
Measurement of Power Question 2 Detailed Solution
In two wattmeter method, the wattmeter readings are given by
W1 = VLIL cos (30 – ϕ)
W2 = VLIL cos (30 + ϕ)
Total power = W1 + W2
Reactive power = √3 (W1 – W2)
Power factor = cos ϕ
Where \(\phi = {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{\left( {{W_1} + {W_2}} \right)}}} \right)\)
Important Point:
p.f. angle (ϕ) |
p.f.(cos ϕ) |
W1 [VLIL cos (30 + ϕ)] |
W2 [VLILcos (30 - ϕ)] |
W = W1 + W2 [W = √3VLIL cos ϕ] |
Observations |
0° |
1 |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
√3 VLIL |
W1 = W2 |
30° |
0.866 |
\(\frac{{{V_L}I}}{2}\) |
VLIL |
1.5 VL IL |
W2 = 2W1 |
60° |
0.5 |
0 |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
W1 = 0 |
90° |
0 |
\(\frac{{ - {V_L}{I_L}}}{2}\) |
\(\frac{{{V_L}{I_L}}}{2}\) |
0 |
W1 = -ve W2 = +ve |
Measurement of Power Question 3:
The wattmeter measures the angle between the current phasor detected by the _________ and the voltage phasor detected by the ____________.
Answer (Detailed Solution Below)
Measurement of Power Question 3 Detailed Solution
In wattmeter, the arrangement of the current coil is in series with the load and the arrangement of the potential coil is across the load.
Hence the wattmeter measures the angle between the current phasor detected by the current coil and the voltage phasor detected by the voltage coil.
The wattmeter measures the average power and it is given by
\(P = {V_{ph}}{I_{ph}}\cos \left( \phi \right)\)
ϕ is the angle between Vph and Iph
Measurement of Power Question 4:
In a three-phase measurement by two-wattmeter method, the readings of the wattmeters are equal in magnitude but opposite in the sign then the nature of the load will be
Answer (Detailed Solution Below)
Measurement of Power Question 4 Detailed Solution
Two wattmeter method:
Two wattmeter method is used to measure the power in three-phase circuits for both balanced and unbalanced load.
The wattmeter readings are
\({W_1} = {V_L}{I_L}\cos \left( {30 - ϕ } \right)\)
\( {W_2} = {V_L}{I_L}\cos \left( {30 + ϕ } \right)\)
\({W_1} + {W_2} = {V_L}{I_L}\left[ {\cos \left( {30 - ϕ } \right) + \cos \left( {30 + ϕ } \right)} \right]\)
\(= \sqrt 3 {V_L}{I_L}\cos ϕ\)
∴Total three-phase power is
\( W= {\rm{\;}}{{\rm{W}}_1} + {{\rm{W}}_2} = \sqrt 3 {V_L}{I_L}\cos ϕ \)
Total three-phase power is the sum of two wattmeters.
\({W_1} = {V_L}{I_L}\cos \left( {30 - ϕ } \right)\)
\({W_2} = {V_L}{I_L}\cos \left( {30 + ϕ } \right)\)
\({W_1} - {W_2} = \sqrt 3 {V_{ph}}{I_{ph}}\sin ϕ\)
\(\sqrt 3 \left( {{W_1} - {W_2}} \right) = 3{V_{ph}}{I_{ph}}\sin ϕ \)
Reactive power \(= \surd 3\;\left( {{W_1}-{W_2}} \right)\)
Reactive power is equal to √3 times the difference between the readings of the two wattmeters.
\({W_1} + {W_2} = 3{V_{ph}}{I_{ph}}\cos ϕ\)
\(\sqrt 3 \left( {{W_1} - {W_2}} \right) = 3{V_{ph}}{I_{ph}}\cos ϕ \)
\(\Rightarrow ϕ = {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)\)
Power factor \(= cos\;ϕ\)
\(cosϕ = \cos \left[ {{{\tan }^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)} \right]\)
Nature of the load based on wattmeter readings:
The nature of the load w.r.t the readings shown in the below table.
Wattmeter readings |
Power factor value |
Nature of the load |
|
W1 |
W2 |
||
W1 = P |
W2 = -P |
Cos ϕ = 0 (ZPF) |
Pure inductive load |
W1 = P |
W2 = P |
Cos ϕ = 1 (UPF) |
Pure resistive load |
W1 = P |
W2 = 0 |
cos ϕ = 0.5 lag |
R-L load |
P = Active power value in Watts
Points to remember:
The value 0 < cos ϕ < 0.5 or 60° < ϕ < 90° means that one of the wattmeters reads negative value.
Measurement of Power Question 5:
In a low power factor wattmeter the pressure coil is connected
Answer (Detailed Solution Below)
Measurement of Power Question 5 Detailed Solution
- In the circuit shown in figure (a), the pressure coil is connected on the supply side of the current coil; The same current passes through the load and current coil of the wattmeter
- But the voltage across the pressure coil is more than that across the load by an amount equal to the voltage drop in the current coil
- This connection is used under light loads (or) where the load impedance is high
- This connection is used for high power factor circuits
- In the circuit shown in figure (b), the pressure coil is connected on the load side of the current coil
- The voltage across the pressure coil is the same as that across the load, but the current in the current coil is more than in the load by an amount equal to the current in the pressure coil
- This connection is used under heavy loads (or) where the load impedance is low
- This connection is used for low power factor circuits
Measurement of Power Question 6:
The current coil of a 200 V, 5 A, electrodynamometer type LPF wattmeter carries a current of \(\sqrt 2 {\rm{cos}}\left( {100\pi t} \right)\) A. The voltage across the pressure coil is \(\sqrt 2 {\rm{sin}}\left( {100\pi t} \right)\) V. The meter will indicate
Answer (Detailed Solution Below)
Measurement of Power Question 6 Detailed Solution
Concept:
The power triangle is shown below.
P = Active power (or) Real power in W = Vrms Irms cos ϕ
Q = Reactive power in VAR = Vrms Irms sin ϕ
S = Apparent power in VA = Vrms Irms
S = P + j Q
\(S = \sqrt {{P^2} + {Q^2}} \)
ϕ is the phase difference between the voltage and current
Power factor \(\cos \phi = \frac{P}{S}\)
Calculation:
Given that,
\(\begin{array}{l} V = \sqrt 2 sin\;\left( {100\pi t} \right)\\ I = \sqrt 2 cos\;\left( {100\pi t} \right) \end{array}\)
The phase difference between V and I is = 90°
Power = VI cos ϕ
P = 0 WMeasurement of Power Question 7:
In a 3-phase system, two-wattmeter method is used to measure the power. If one of the wattmeters shows a negative reading and the other shows a positive reading, and the magnitude of the readings are not the same, then what will be the power factor (p.f.) of the load?
Answer (Detailed Solution Below)
Measurement of Power Question 7 Detailed Solution
Concept:
In a two-wattmeter method,
The reading of first wattmeter (W1) = VL IL cos (30 – ϕ)
The reading of second wattmeter (W2) = VL IL cos (30 + ϕ)
Total power in the circuit (P) = W1 + W2
Total reactive power in the circuit \(Q = \sqrt 3 \left( {{W_1} - {W_2}} \right)\)
Power factor = cos ϕ
\(ϕ = {\rm{ta}}{{\rm{n}}^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)\)
p.f. angle (ϕ) |
p.f.(cos ϕ) |
W1 [VLIL cos (30 - ϕ)] |
W2 [VLIL cos (30 + ϕ)] |
W = W1 + W2 [W = √3VLIL cos ϕ] |
Observations |
0° |
1 |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
√3 VLIL |
W1 = W2 |
30° |
0.866 |
\(\frac{{{V_L}I_L}}{2}\) |
VLIL |
1.5 VL IL |
W1= 2W2 |
60° |
0.5 |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
0 |
\(\frac{{\sqrt 3 }}{2}{V_L}{I_L}\) |
W2 = 0 |
90° |
0 |
\(\frac{{ - {V_L}{I_L}}}{2}\) |
\(\frac{{{V_L}{I_L}}}{2}\) |
0 |
W2 = -ve W1 = +ve |
Explanation:
W1 = -ve, W2 = +ve
|W1| ≠ |W2|, then the powere factor range is given as
The range of ϕ is, 60 < ϕ < 90
Now the range of power factor is, 0.5 > cos ϕ > 0.
Measurement of Power Question 8:
In the two-wattmeter method of three phase power measurement of a balanced load, if the reading of one metre is – 200 W, then then power factor of the load is ______.
Answer (Detailed Solution Below)
Measurement of Power Question 8 Detailed Solution
In two wattmeter method, the power factor is given by
\(cos\phi = \cos \left[ {{{\tan }^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)} \right]\)
Here, \(\phi = {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)\)
Given that, one reading is negative.
Hence the term (W1 + W2) is always lesser than (W1 - W2).
Now the minimum value of the term \(\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}\) is √3 and it occurs at one of the reading is zero. Here no reading is zero. Hence the value should be greater than √3 and hence ϕ will be greater than 60°.
Now the maximum value of the term \(\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}\) is infinite and it occurs at (W1 = -W2). In this case ϕ will be 90°.
Hence ϕ varies between 60 to 90 degrees.
Now the range of ϕ is, \(60^\circ < \phi < 90^\circ \)
Now the range of power factor is, \(0.5 > \cos \phi > 0\).
The power factor of the system is greater than or equal to 0 but less than 0.5.
Measurement of Power Question 9:
What are the signs of wattmeter W1 and W2 , respectively, if the power factor of the system is 0.5?
Answer (Detailed Solution Below)
Measurement of Power Question 9 Detailed Solution
The correct answer is option 4):
Concept:
Two wattmeter method:
- The two-wattmeter method uses two voltage measurements referenced to the same phase (line) and the two currents flowing into that phase. The assumption is that the three-phase system is balanced, i.e., the summation of all voltages = 0 V and the summation of all currents = 0 A.
- This is true if there is no leakage current from neutral to ground.
Reading of both wattmeters are
W1 = √3 VpIpcos (30 - ϕ )
W2 = √3 VpIpcos (30 + ϕ)
where Vp → Voltage across pressure coil I
p → Current through coil ϕ → Phase angle
\(\mathrm{Power\, Factor} = \cos \phi = \cos\left [ \tan^{-1}\sqrt{3}\left ( \frac{w_{1}-w_{2}}{w_{1}+w_{2}} \right ) \right ]\)
- The result can be summarised as At zero power factor lagging, W1 reads the positive value and W2 reads the negative value.
- For power factors lying between 0 to 0.5 lagging, W1 reads the positive value and W2 reads the negative value.
- At 0.5 power factor lagging, W1 reads the positive value and W2 reads the zero value.Hence option 4 is correct
- For power factors lying between 0.5 to 1 lagging, W1 reads the positive value and W2 reads the positive value.
- At unity power factor lagging, W1 reads the positive value and W2 reads the positive value.
Measurement of Power Question 10:
The two wattmeter method is used to measure power in a three-phase system when ______.
Answer (Detailed Solution Below)
Measurement of Power Question 10 Detailed Solution
- The one-wattmeter method is used for the measurement of three-phase power in case balanced loads only
- It is used for both star and delta connected loads
- Two wattmeter method and three wattmeter methods are used for both balanced and unbalanced loads
- Two wattmeter method is best suitable for three-phase three-wire system and three wattmeter method is suitable for the three-phase four-wire system