Download Solution PDFAccording to IS (Indian Standard) Specification 1180-1964 for outdoor type distribution transformer, the conservator is provided on transformer rating _______.
Answer (Detailed Solution Below)
Detailed Solution
Download Solution PDFThe correct answer is option 2.
Requirements as per IS (Indian Standard) Specification for transformers up to 100 KVA
1.) No. of tappings
- Upto 25 kVA: 2 by means of links
- Greater than 25 kVA: 5 by means of an external switch
2.) Conservator and thermometer pocket for transformer above the rating of 50 kVA
3.) The minimum clearance of 75 mm and 40 mm for phase-to-phase and phase-to-earth must be available on the LV side of the transformer.
4.) The minimum clearance of 255 mm and 140 mm for phase-to-phase and phase-to-earth must be available on the HV side of the transformer.
5.) The maximum temperature rise must not exceed 55° C.